Industrial IoT
A tag moves by 0.3 degrees each sample. When does its deadband report?
For OPC UA absolute deadband, compare the current sample with the last value pushed to the queue and follow the strict greater-than threshold.
For an OPC UA absolute deadband of 1.0 °C, many small changes can eventually cause a notification even when no single sample-to-sample step exceeds the threshold. The comparison is against the last value pushed to the queue. The specified change test is strictly greater than the deadband. An exactly 1.0 °C difference does not pass that value-change test.
Trace the reference as well as the temperature
Begin with 20.0 °C already queued. Readings of 20.3, 20.6 and 21.0 remain within or exactly at the threshold. A sample of 21.2 differs by 1.2 °C, so it is pushed and becomes the new reference. The next sample of 20.5 is only 0.7 °C from 21.2. A later 19.9 differs by 1.3 °C and triggers again.

Worked data
Sample temperature | Reference before sample (°C) | Absolute difference (°C) |
20.3 °C | 20.0 | 0.3 |
20.6 °C | 20.0 | 0.6 |
21.0 °C | 20.0 | 1.0 |
21.2 °C | 20.0 | 1.2 |
20.5 °C | 21.2 | 0.7 |
19.9 °C | 21.2 | 1.3 |
Download the figures in this worked example (CSV)
Separate value suppression from lost communications
A quiet subscription can mean a stable signal or movement inside the deadband. The last plotted value by itself cannot distinguish those cases. Check connection health and source status separately. Status changes can have their own notification behaviour according to the configured trigger.
Use the server’s supported DataChangeFilter, engineering units and revised settings. An absolute threshold in degrees is different from a percentage-of-range deadband. Where the exact equality boundary matters, account for floating-point representation and test a value clearly on each side as well as equality. Keep an unfiltered reference trace during an authorised offline commissioning test so the resulting gaps are explainable.
Choose a threshold against an actual reporting decision
A team interested in daily heating cycles may accept a sparse series that retains major swings. A team measuring residence time above a narrow process threshold may need finer sampling, a smaller deadband or an independent event record. If a reporting threshold sits between two stored values, the crossing time is only constrained by the observations available.
Imagine the signal moves from 20.0 to 20.9 °C and remains there. Under the example 1.0 °C deadband it generates no value-change message. A trend drawn from the last recorded point can continue to show 20.0 °C even though the source has settled at 20.9 °C. If that distinction changes a production decision, reducing the chart's display grid spacing will achieve nothing. The information was suppressed upstream.
During validation, keep the source samples and the monitored-item output with comparable timestamps. Work through the reporting decision on both traces, including slow ramps, reversals, repeated values and a change of quality. Also record the number of messages and storage volume: a smaller deadband can recover detail while changing historic storage and network demand. Choose the threshold using that trade-off and the decision the record needs to support.
Sources
OPC Foundation · DataChangeFilter and deadband, part 4
Cover illustration by Industry Applied, generated with AI. A temperature instrument on a plant return line.
For an OPC UA absolute deadband of 1.0 °C, many small changes can eventually cause a notification even when no single sample-to-sample step exceeds the threshold. The comparison is against the last value pushed to the queue. The specified change test is strictly greater than the deadband. An exactly 1.0 °C difference does not pass that value-change test.
Trace the reference as well as the temperature
Begin with 20.0 °C already queued. Readings of 20.3, 20.6 and 21.0 remain within or exactly at the threshold. A sample of 21.2 differs by 1.2 °C, so it is pushed and becomes the new reference. The next sample of 20.5 is only 0.7 °C from 21.2. A later 19.9 differs by 1.3 °C and triggers again.

Worked data
Sample temperature | Reference before sample (°C) | Absolute difference (°C) |
20.3 °C | 20.0 | 0.3 |
20.6 °C | 20.0 | 0.6 |
21.0 °C | 20.0 | 1.0 |
21.2 °C | 20.0 | 1.2 |
20.5 °C | 21.2 | 0.7 |
19.9 °C | 21.2 | 1.3 |
Download the figures in this worked example (CSV)
Separate value suppression from lost communications
A quiet subscription can mean a stable signal or movement inside the deadband. The last plotted value by itself cannot distinguish those cases. Check connection health and source status separately. Status changes can have their own notification behaviour according to the configured trigger.
Use the server’s supported DataChangeFilter, engineering units and revised settings. An absolute threshold in degrees is different from a percentage-of-range deadband. Where the exact equality boundary matters, account for floating-point representation and test a value clearly on each side as well as equality. Keep an unfiltered reference trace during an authorised offline commissioning test so the resulting gaps are explainable.
Choose a threshold against an actual reporting decision
A team interested in daily heating cycles may accept a sparse series that retains major swings. A team measuring residence time above a narrow process threshold may need finer sampling, a smaller deadband or an independent event record. If a reporting threshold sits between two stored values, the crossing time is only constrained by the observations available.
Imagine the signal moves from 20.0 to 20.9 °C and remains there. Under the example 1.0 °C deadband it generates no value-change message. A trend drawn from the last recorded point can continue to show 20.0 °C even though the source has settled at 20.9 °C. If that distinction changes a production decision, reducing the chart's display grid spacing will achieve nothing. The information was suppressed upstream.
During validation, keep the source samples and the monitored-item output with comparable timestamps. Work through the reporting decision on both traces, including slow ramps, reversals, repeated values and a change of quality. Also record the number of messages and storage volume: a smaller deadband can recover detail while changing historic storage and network demand. Choose the threshold using that trade-off and the decision the record needs to support.