What a 10% fan speed change does to power
The fan affinity laws give a starting estimate for a ventilation trial. Compare the predicted motor demand with measured airflow and real input power.

A variable-speed fan is running continuously at a packing plant. Production asks whether turning it down slightly would save much electricity. The useful answer is a pair of readings: how much power the change saves and whether the process still gets the air it needs.
Predict the change, then test the duty
Under similar conditions for the same fan, airflow follows speed, pressure follows speed squared and shaft power follows speed cubed. A fixed pressure requirement, damper controls or a change in efficiency can move the actual result. Choose an ordinary process ventilation duty and agree the acceptable airflow with the process owner before the test.
At 90% of original speed, the ideal shaft-power ratio is 0.90³ = 0.729. Starting from 20 kW of shaft power gives about 14.6 kW. This is a prediction at the fan shaft. Compare a separately measured pair of electrical input readings with each other at the two settings.

What to check on site
Record fan speed, damper position, airflow, pressure and electrical input together.
Keep filter condition and the production state comparable across both runs.
Use a stable interval and record which process criteria were met at each speed.
Treat smoke extraction and safety-related ventilation as engineered systems with their own performance requirements. A routine efficiency trial belongs on a duty where the site has approved the operating range.
Sources and photograph
US Department of Energy — fan system performance sourcebook
A variable-speed fan is running continuously at a packing plant. Production asks whether turning it down slightly would save much electricity. The useful answer is a pair of readings: how much power the change saves and whether the process still gets the air it needs.
Predict the change, then test the duty
Under similar conditions for the same fan, airflow follows speed, pressure follows speed squared and shaft power follows speed cubed. A fixed pressure requirement, damper controls or a change in efficiency can move the actual result. Choose an ordinary process ventilation duty and agree the acceptable airflow with the process owner before the test.
At 90% of original speed, the ideal shaft-power ratio is 0.90³ = 0.729. Starting from 20 kW of shaft power gives about 14.6 kW. This is a prediction at the fan shaft. Compare a separately measured pair of electrical input readings with each other at the two settings.

What to check on site
Record fan speed, damper position, airflow, pressure and electrical input together.
Keep filter condition and the production state comparable across both runs.
Use a stable interval and record which process criteria were met at each speed.
Treat smoke extraction and safety-related ventilation as engineered systems with their own performance requirements. A routine efficiency trial belongs on a duty where the site has approved the operating range.